The Type C Densimeter enables continuous measurement of the density of substances transported through pipelines, as well as other properties of these substances calculated based on the measured density.
Applications in process control automation systems:
Flotation processes
Coal enrichment in heavy media
Water-slurry circuits
Preparation and transport of backfill mixtures
The type C Densimeter offers:
A modern design adaptable to the technical conditions of a given facility
High operational reliability
Maintenance-free measuring sensor
FULL OPERATIONAL SAFETY – virtually no restricted access zone, due to the use of a very low-activity isotope (approximately 20 to 30 times lower than in other densitometers)
Specification
Metrological parameters:
Measurement method: Gamma radiation absorption
Measured substance pressure: ≤1 MPa (≤1.6 MPa)
Measured substance temperature: 0°C – 60°C
Density measurement range: 0.1 – 2.5 g/cm³
Measurement errors – standard deviations:
Two-component substances:
Density: ±0.0005 g/cm³
Concentration: ±1.0 g/liter
Three-component substances:
Density: ±0.001 g/cm³
Concentration: ±5 – 10 g/liter
Source decay correction: Automatic every 7 days
Radiation source: ¹³⁷Cs with an activity of 37–555 MBq (1–10 mCi)